In software versions 13B40 and below, the Humidity Sensor Alarm occurs when the humidity exceeds 90% or when the sensor is disconnected. Humidity alarm only occurs if the sensor is disconnected in software versions after 13B40.
Troubleshooting
Possible Cause | Component to Check | Recommended Action |
Low heat load, site cools down without compressor | Free cooling humidity limit (U04 in L04 Menu) | Change to 80%. For extremely small heat load site, change to 60%. |
Loose/incorrect sensor wire | Sensor wire | Correct wiring. Refer to the Humidity Sensor Wiring diagram and reference the helpdesk article: Reconnecting a Loose Humidity Sensor |
Defective humidity sensor | Humidity sensor | Replace Humidity Sensor |