The A29/A30 alarm only applies to DC powered supply fans. If this alarm is displayed when AC fans are installed, change the SF1 setting in the D menu from 0 to 1 or from AUT/DC to AC. If using the PGD, change option Ch1 in the Manufacturer Menu to AC. See Chapter 1: Model Identification to determine supply fan power input.
When the DC fan is running, pressure is built up across the air pressure differential switches (PF2 & PF3) and the circuit between terminals 5 & 9 will close. If the pressure switch does not close after 60 seconds, A29/30 will trigger, indicating problems with the supply fan.
Troubleshooting
Possible Cause | Component to Check | Recommended Action |
No power to DC fan | Verify 48VDC presence on DC breaker. Verify 48VDC across 12 and 131 to the supply fan | Correct DC power supply. |
Incorrect DC polarity | Placing the red probe on the +48 terminal and the black probe on the -48 terminal should give a +48VDC reading. Verify controller side as well. | Correct DC polarity. |
No speed signal to DC fan | Speed signal between 11 and 12. | Verify 0-10 VDC signal between terminal 11 and 12. |
Incorrect alarm wiring | Alarm wiring | Verify wiring. See DC Fan Air Flow Alarm Wiring. |
Faulty air pressure differential switch | Air pressure differential switch should close when the fan is running at high speed | Replace air pressure differential switch. |