Remote Parameter Settings
Index
New Value
Current
Description
1
<%var(0,2,6)%> ℉ FC Minimum Fan Speed Setpoint (must be < max fan speed setpoint)
2
<%var(0,2,5)%> ℉ FC Maximum Fan Speed Setpoint (must be < high temp alarm setpoint)
3
<%var(0,2,7)%> ℉ AC1 Start Setpoint (must be < high temp alarm setpoint)
4
<%var(0,2,8)%> ℉ AC1 Stop Setpoint (must be < AC1 start setpoint)
5
<%var(0,2,9)%> ℉ AC2 Start Setpoint (must be < high temp alarm setpoint)
6
<%var(0,2,10)%> ℉ AC2 Stop Setpoint (must be < AC2 start setpoint)
7
<%var(0,2,114)%> ℉ Low Temp Alarm Setpoint
8
<%var(0,2,113)%> ℉ High Temp Alarm Setpoint
9
<%var(0,2,115)%> ℉ Heater Start Setpoint (must be > low temp alarm setpoint)
10
<%var(0,2,116)%> ℉ Heater Stop Setpoint (must be > heater start setpoint)
11
<%var(0,2,121)%> ℉ Minimum Temperature Difference for Free Cooling
12
 
Enable Partial FC (Continue FC while AC is On if conditions remain favorable)
Unit Type: FCB